Convert Pt100, Pt500 and Pt1000 resistance to temperature

Convert ohms to °C or °C to ohms, with the tolerance band, lead-wire error and a resistance table.

  • Runs on your device
  • No sign-up
  • Works offline after a visit
Direction

Two-wire lead resistance

Resistance at — — —
—tolerance band, ± °C
—two-wire lead error, °C
—R₀ at 0 °C, Ω
—α, per °C
Resistance table around this point
°CΩ°F

IEC 60751 platinum curve, −200 to 850 °C. Values outside that range are mathematical extrapolations and are flagged.

How to convert a Pt100 resistance

  1. Choose the sensor (Pt100, Pt500 or Pt1000) and the direction: temperature to resistance, or resistance to temperature.
  2. Type a temperature in °C or °F, or an ohms reading; the converted value, tolerance band and two-wire lead error appear live.
  3. Read the R–t curve with your point marked and the resistance table around that temperature.

Questions

Which formula is used?

IEC 60751 uses the Callendar–Van Dusen equation. From 0 to 850 °C, R = R₀(1 + A·t + B·t²); from −200 to 0 °C, R = R₀(1 + A·t + B·t² + C(t − 100)t³). The constants are A = 3.9083×10⁻³, B = −5.775×10⁻⁷ and C = −4.183×10⁻¹² per °C, with R₀ = 100, 500 or 1000 Ω. Above 0 °C the calculator inverts the quadratic directly; below 0 °C it solves the cubic by Newton iteration.

What is the sensor’s measuring range?

The standard defines the platinum RTD curve from −200 to 850 °C. Values outside that span are flagged because the coefficients are not defined there and a real probe may not survive the temperature. This tool reports the mathematical result but tells you when it is outside the standard’s range.

What do the tolerance classes mean?

IEC 60751 tolerance class AA allows ±(0.1 + 0.0017·|t|) °C, class A ±(0.15 + 0.002·|t|) °C, class B ±(0.3 + 0.005·|t|) °C and class C ±(0.6 + 0.01·|t|) °C, with t in °C. These are the limits for a new, undamaged sensor; wiring, self-heating and calibration errors come on top.

How is the two-wire lead error worked out?

In a two-wire connection the lead resistance adds to the sensor resistance. The calculator converts R + 2·r_lead back to a temperature (two wires carry the measurement current) and subtracts the true temperature to get the error. Three- and four-wire connections cancel most of this; the figure here applies only to the two-wire case.