Calculate cable voltage drop and wire size
Size the cable from length, current and allowable drop, with the formula shown beside the answer.
- Runs on your device
- No sign-up
- Works offline after a visit
Conductor
Standard sizes and the drop they give
| mm² | AWG ≈ | Drop, V | Drop, % | Loss, W |
|---|
Straight-conductor resistance at the chosen temperature. Reactance is an assumption, and ampacity, fault current and local wiring rules are not checked.
How to calculate cable voltage drop
- Pick DC, single-phase or three-phase, then enter the length, current and supply voltage.
- Choose copper or aluminium, the conductor temperature and a cable size in mm² or AWG.
- Read the volts dropped, the drop percentage and the smallest standard size that meets your limit.
Questions
What formulas does it use?
DC and single-phase use ΔV = 2·I·L·R (the out and return conductors), three-phase uses ΔV = √3·I·L·(R·cosφ + X·sinφ), where R is the resistance of one conductor in Ω/m and X its reactance in Ω/m. Load voltage is the supply voltage minus ΔV, and cable loss is I²·R·L per conductor, doubled for DC and single-phase and multiplied by three for three-phase.
Where do the resistance numbers come from?
ρ = 0.017241 Ω·mm²/m for copper and 0.028264 Ω·mm²/m for aluminium at 20 °C, corrected as ρ(T) = ρ₂₀·[1 + α·(T − 20)], with α = 0.00393 per °C for copper and 0.00403 for aluminium. Resistance per metre is ρ divided by the conductor cross-section in mm². These are ideal straight-conductor values; no skin effect, proximity effect or connection resistance is included.
What is assumed about reactance?
Three-phase calculations use a reactance of 0.08 mΩ/m (0.00008 Ω/m) by default, a common rough value for low-voltage cables. It is an editable assumption: the real value depends on conductor spacing, cable construction and frequency. For short, small cables the resistive term dominates, so changing it makes little difference.
Which sizes and drop limits are offered?
Metric sizes run from 0.5 to 300 mm² and the AWG list from 24 AWG to 4/0, converted using each gauge’s nominal cross-section. The 3% and 5% limits are common design targets, not a substitute for the wiring rules in your country: branch circuits, feeders, lighting and long runs can have different limits, and other constraints such as ampacity and fault loop impedance also size a cable.