Scale 4–20 mA and other analog signals
Type a current, a voltage, a percentage or a process value: every other scale follows.
- Runs on your device
- No sign-up
- Works offline after a visit
| Percent | Signal | Engineering | Raw |
|---|
How to scale a 4–20 mA signal
- Pick the input range, such as 4–20 mA or 0–10 V, and set the engineering range at the sensor.
- Type a value in any of the three live boxes: signal, percent or engineering units.
- Read the PLC raw counts, the fault-band status and the maximum loop resistance for your supply.
Questions
How is the scaling worked out?
The signal is mapped linearly: percent = (value − low signal) ÷ (high signal − low signal) × 100, and engineering value = low engineering + percent ÷ 100 × (high engineering − low engineering). Typing in either direction inverts the same line. Raw counts use the same fraction over the chosen ADC span.
What do the Siemens and other raw ranges mean?
Some controllers report a 4–20 mA input as 0–27648 counts, others as 0–32000 or 4000–20000 (where 4 mA lands on 4000). The calculator uses the span you pick: 4 mA is the low count and 20 mA the high count. Values below the low count are clamped for the display, so a live fault current is shown by the fault band rather than a nonsensical engineering value.
What is NAMUR NE43?
NE43 recommends that a transmitter keep its normal signal inside 3.8–20.5 mA and drive the output outside that band to report a fault. Currents below 3.6 mA or above 21 mA are the failure range; the narrow bands from 3.6 to 3.8 and 20.5 to 21 mA are outside the normal signal range. The check only applies when the chosen signal is 4–20 mA.
How is loop resistance calculated?
A two-wire loop can spare (supply voltage − transmitter minimum voltage) ÷ 0.02 A of resistance at 20 mA, including the wire and the receiver resistor. The result is an ideal upper bound: cable temperature, other loads and the transmitter’s actual requirements need checking on site.