Plant-floor numbers: takt time, OEE, 4–20 mA, PT100 and more
Most plant-floor questions come down to a short formula and a unit you have to get right: how fast must a line run to meet demand, what share of the time was it productive, what does 12 mA mean on this sensor. Each section below states the question, the formula and one worked example, and links to the tool that does the sum while you type. All of them run in your browser and send nothing anywhere.
Takt time calculatorCan the line meet demand?Do it freeTakt time: how often must a part leave the line?
Takt time is the available production time divided by customer demand. A shift of 480 minutes with 30 minutes of breaks has 450 minutes, which is 27,000 seconds. If the customer wants 300 parts in that shift, takt time is 27,000 ÷ 300 = 90 seconds per part. The takt time calculator does this sum from the shift length, breaks, planned stops and daily demand. List each station's cycle time and it also shows the bottleneck and which stations exceed takt. If a station takes longer than the takt, that station is where the line falls behind.
OEE: how much of the time was really productive?
Overall equipment effectiveness is availability × performance × quality. With availability 90 percent, performance 95 percent and quality 98 percent, OEE is 0.90 × 0.95 × 0.98 = 0.8379, or 83.8 percent. The OEE calculator works out availability, performance and quality from planned time, downtime, ideal cycle time and unit counts, shows where the lost time went, and lets you set a target for each factor to see which improvement lifts OEE the most.
4–20 mA: from current to engineering units
A transmitter scaled 0 to 10 bar sends 4 mA at 0 bar and 20 mA at 10 bar. At 12 mA the reading is (12 − 4) ÷ 16 = 0.5 of the span, which is 5 bar. A current below 4 mA is a fault signal on most devices, not a low reading. The analog signal scaling tool converts both ways between mA, percent and engineering units.
PT100: from resistance to temperature
A PT100 sensor reads 100 Ω at 0 °C and 138.51 Ω at 100 °C (IEC 60751). The relation is close to linear, with a coefficient of about 0.385 Ω per °C near 0 °C, but not exactly, so the standard uses a polynomial. The PT100 calculator converts between resistance and temperature for Pt100, Pt500 and Pt1000 sensors, and shows the tolerance band, the error from two-wire lead resistance and a resistance table around your point.
Three-phase power: kilowatts from volts and amps
Real power in a balanced three-phase load is √3 × line voltage × line current × power factor. At 400 V, 20 A and a power factor of 0.85 that is 1.732 × 400 × 20 × 0.85 = 11,778 W, or about 11.8 kW. The three-phase power calculator takes the line voltage and power factor and one known value (kW, kVA, amps or horsepower), then gives the others with the formula. It also covers single-phase and DC.
Voltage drop: will the far end get enough?
For copper at 0.0175 Ω·mm² per metre, a 2.5 mm² conductor over 50 m has a resistance of 0.0175 × 50 ÷ 2.5 = 0.35 Ω. At 16 A in a three-phase circuit the drop is √3 × 16 × 0.35 = 9.7 V, which is 2.4 percent of 400 V. This counts resistance only and leaves out reactance, which matters on long, large cables. The voltage drop calculator lets you try a larger cross-section before you order the cable.
Modbus: two registers, one number
Many devices send a 32-bit floating point value across two 16-bit holding registers. The registers 0x41C8 and 0x0000 together are 0x41C80000, which decodes to 25.0. If the device sends the low word first, you read garbage until you swap the order. The Modbus register decoder turns register values into numbers, so you can try the byte orders until the result looks believable.
Quick answers
Which one do I check first on a slow line?
Takt time tells you the pace the demand needs, and OEE tells you the pace you reach. Compare the two.
Do these calculators use anything from a server?
No. The numbers stay in the page.
Are these values safe to design a circuit from?
Treat them as a check. Cable and protection sizing follows your local wiring standard and the manufacturer's data sheet.