# Calculate cable voltage drop and wire size

> Size the cable from length, current and allowable drop, with the formula shown beside the answer.

Work out voltage drop, load voltage and cable loss for DC, single-phase and three-phase circuits in copper or aluminium, then find the smallest cable.

- Tool: [Voltage drop calculator](https://fixmint.cc/voltage-drop-calculator)
- Category: [Industrial & networks](https://fixmint.cc/industrial)
- Fixes: Is this cable too thin?
- Runs in the browser: files and text stay on the device, no sign-up, free.

## How to calculate cable voltage drop

1. Pick DC, single-phase or three-phase, then enter the length, current and supply voltage.
2. Choose copper or aluminium, the conductor temperature and a cable size in mm² or AWG.
3. Read the volts dropped, the drop percentage and the smallest standard size that meets your limit.

## Questions

### What formulas does it use?

DC and single-phase use ΔV = 2·I·L·R (the out and return conductors), three-phase uses ΔV = √3·I·L·(R·cosφ + X·sinφ), where R is the resistance of one conductor in Ω/m and X its reactance in Ω/m. Load voltage is the supply voltage minus ΔV, and cable loss is I²·R·L per conductor, doubled for DC and single-phase and multiplied by three for three-phase.

### Where do the resistance numbers come from?

ρ = 0.017241 Ω·mm²/m for copper and 0.028264 Ω·mm²/m for aluminium at 20 °C, corrected as ρ(T) = ρ₂₀·[1 + α·(T − 20)], with α = 0.00393 per °C for copper and 0.00403 for aluminium. Resistance per metre is ρ divided by the conductor cross-section in mm². These are ideal straight-conductor values; no skin effect, proximity effect or connection resistance is included.

### What is assumed about reactance?

Three-phase calculations use a reactance of 0.08 mΩ/m (0.00008 Ω/m) by default, a common rough value for low-voltage cables. It is an editable assumption: the real value depends on conductor spacing, cable construction and frequency. For short, small cables the resistive term dominates, so changing it makes little difference.

### Which sizes and drop limits are offered?

Metric sizes run from 0.5 to 300 mm² and the AWG list from 24 AWG to 4/0, converted using each gauge’s nominal cross-section. The 3% and 5% limits are common design targets, not a substitute for the wiring rules in your country: branch circuits, feeders, lighting and long runs can have different limits, and other constraints such as ampacity and fault loop impedance also size a cable.