# Convert Pt100, Pt500 and Pt1000 resistance to temperature

> Convert ohms to °C or °C to ohms, with the tolerance band, lead-wire error and a resistance table.

Convert Pt100, Pt500 and Pt1000 resistance to temperature and back to IEC 60751, with the formula, tolerance band, two-wire lead error and a resistance table.

- Tool: [Pt100 calculator](https://fixmint.cc/pt100-calculator)
- Category: [Industrial & networks](https://fixmint.cc/industrial)
- Fixes: What temperature is this resistance?
- Runs in the browser: files and text stay on the device, no sign-up, free.

## How to convert a Pt100 resistance

1. Choose the sensor (Pt100, Pt500 or Pt1000) and the direction: temperature to resistance, or resistance to temperature.
2. Type a temperature in °C or °F, or an ohms reading; the converted value, tolerance band and two-wire lead error appear live.
3. Read the R–t curve with your point marked and the resistance table around that temperature.

## Questions

### Which formula is used?

IEC 60751 uses the Callendar–Van Dusen equation. From 0 to 850 °C, R = R₀(1 + A·t + B·t²); from −200 to 0 °C, R = R₀(1 + A·t + B·t² + C(t − 100)t³). The constants are A = 3.9083×10⁻³, B = −5.775×10⁻⁷ and C = −4.183×10⁻¹² per °C, with R₀ = 100, 500 or 1000 Ω. Above 0 °C the calculator inverts the quadratic directly; below 0 °C it solves the cubic by Newton iteration.

### What is the sensor’s measuring range?

The standard defines the platinum RTD curve from −200 to 850 °C. Values outside that span are flagged because the coefficients are not defined there and a real probe may not survive the temperature. This tool reports the mathematical result but tells you when it is outside the standard’s range.

### What do the tolerance classes mean?

IEC 60751 tolerance class AA allows ±(0.1 + 0.0017·|t|) °C, class A ±(0.15 + 0.002·|t|) °C, class B ±(0.3 + 0.005·|t|) °C and class C ±(0.6 + 0.01·|t|) °C, with t in °C. These are the limits for a new, undamaged sensor; wiring, self-heating and calibration errors come on top.

### How is the two-wire lead error worked out?

In a two-wire connection the lead resistance adds to the sensor resistance. The calculator converts R + 2·r_lead back to a temperature (two wires carry the measurement current) and subtracts the true temperature to get the error. Three- and four-wire connections cancel most of this; the figure here applies only to the two-wire case.

## Related tools

- [Analog signal scaling](https://fixmint.cc/analog-signal-scaling): What does 12 mA mean?
- [Voltage drop calculator](https://fixmint.cc/voltage-drop-calculator): Is this cable too thin?
- [Unit converter](https://fixmint.cc/unit-converter): What is that in metric?