# Work out Modbus polling load

> Estimate frame bytes, bus load and the shortest poll interval for RTU or TCP.

Estimate requests, frame bytes and bus load for Modbus RTU or TCP. Plan register groups and see the shortest interval the line can carry, in your browser.

- Tool: [Modbus polling calculator](https://fixmint.cc/modbus-polling-calculator)
- Category: [Industrial & networks](https://fixmint.cc/industrial)
- Fixes: Will my Modbus line keep up
- Runs in the browser: files and text stay on the device, no sign-up, free.

## How to work out Modbus polling load

1. Pick RTU or TCP and set the line: baud rate, parity, turnaround delay, link speed or latency.
2. Add a row for each register block: device, function, start address, count and poll interval.
3. Read the cycle time, bus load and the shortest interval the line can carry.

## Questions

### Does this talk to my device?

No. The figures are static estimates from the frame sizes and the settings you enter. Nothing is sent, no port is opened, no bus is scanned, and nothing leaves your browser.

### What do the frame sizes include?

Modbus RTU counts 1 address byte and 2 CRC bytes per frame at 11 bits per character with parity or 10 without, plus the 3.5-character gap. Modbus TCP counts a 7-byte MBAP header and the PDU, with the TCP/IP and Ethernet bytes and the round-trip latency as separate settings.

### How are large ranges split?

At most 125 registers per read (functions 03 and 04) and 2000 coils or discrete inputs (functions 01 and 02). A larger count is split into several requests, and ranges on the same device, function and interval are merged when the gap between them fits your merge gap.

### Why is the load over 100%?

The rows ask for more traffic than one poll interval allows. Raise an interval, lower a count, or raise the baud rate or link speed. The result also shows the shortest interval a full pass needs.

## Related tools

- [OEE calculator](https://fixmint.cc/oee-calculator): What is the line really achieving?
- [Webhook signature tester](https://fixmint.cc/webhook-signature-tester): Webhook signature check fails
- [Cron explainer](https://fixmint.cc/cron-expression-explainer): Cron runs at the wrong time
- [Modbus register decoder](https://fixmint.cc/modbus-register-decoder): What do these registers mean?
