# Scale 4–20 mA and other analog signals

> Type a current, a voltage, a percentage or a process value: every other scale follows.

Convert between 4–20 mA, volts, percent and engineering units in both directions, with PLC raw counts, NAMUR NE43 fault bands and the loop burden check.

- Tool: [Analog signal scaling](https://fixmint.cc/analog-signal-scaling)
- Category: [Industrial & networks](https://fixmint.cc/industrial)
- Fixes: What does 12 mA mean?
- Runs in the browser: files and text stay on the device, no sign-up, free.

## How to scale a 4–20 mA signal

1. Pick the input range, such as 4–20 mA or 0–10 V, and set the engineering range at the sensor.
2. Type a value in any of the three live boxes: signal, percent or engineering units.
3. Read the PLC raw counts, the fault-band status and the maximum loop resistance for your supply.

## Questions

### How is the scaling worked out?

The signal is mapped linearly: percent = (value − low signal) ÷ (high signal − low signal) × 100, and engineering value = low engineering + percent ÷ 100 × (high engineering − low engineering). Typing in either direction inverts the same line. Raw counts use the same fraction over the chosen ADC span.

### What do the Siemens and other raw ranges mean?

Some controllers report a 4–20 mA input as 0–27648 counts, others as 0–32000 or 4000–20000 (where 4 mA lands on 4000). The calculator uses the span you pick: 4 mA is the low count and 20 mA the high count. Values below the low count are clamped for the display, so a live fault current is shown by the fault band rather than a nonsensical engineering value.

### What is NAMUR NE43?

NE43 recommends that a transmitter keep its normal signal inside 3.8–20.5 mA and drive the output outside that band to report a fault. Currents below 3.6 mA or above 21 mA are the failure range; the narrow bands from 3.6 to 3.8 and 20.5 to 21 mA are outside the normal signal range. The check only applies when the chosen signal is 4–20 mA.

### How is loop resistance calculated?

A two-wire loop can spare (supply voltage − transmitter minimum voltage) ÷ 0.02 A of resistance at 20 mA, including the wire and the receiver resistor. The result is an ideal upper bound: cable temperature, other loads and the transmitter’s actual requirements need checking on site.

## Related tools

- [Pt100 calculator](https://fixmint.cc/pt100-calculator): What temperature is this resistance?
- [Electricity cost calculator](https://fixmint.cc/electricity-cost-calculator): What does it cost to run?
- [Modbus polling calculator](https://fixmint.cc/modbus-polling-calculator): Will my Modbus line keep up